Kyoritsu KEW 5020 LOGGER
Brand :
Kyoritsu
Categories :
Loggers-Power Meters-PQA
3 channel inputs for the simultaneous recording of Leakage Current , Load Current and Voltage
• Power Quality analysis• Large capacity for storing 60,000 data points
• Lowpass Filter will filter out the harmonics
• LED flickers when the preset current/voltage value is exceeded
• CALL: Confirmation of recorded data
• Selection of One-time mode or Endless mode
• Non Volatile Memory
• Battery power indicator
• The userfriendly PC software "KEW LOG Soft 2" is supplied
• Continuous measuring time: Approx. 10 days (Alkaline Battery)
Specifications
-
20,000 data 30,000 data
60,000 data
-
Using all 3 channels Using 2 channels
Using only 1 channel
-
OS
Windows® 11/10
-
Others
With CD-ROM drive and USB port
-
Display
XGA (1024x768 dots) or more
-
Hard-disk
Space required 100Mbyte or more
-
OS
Windows® 11/10
-
Others
With CD-ROM drive and USB port
-
Display
XGA (1024x768 dots) or more
-
Hard-disk
Space required 100Mbyte or more
-
Range
RMS Accuracy
-
100.0mA
±2.0%rdg±0.9%f.s.+ Accuracy of Sensor
-
Crest Factor
2.5 or less: RMS accuracy (sine) + 2%rdg + 1%f.s.
-
Other ranges
±1.5%rdg±0.7%f.s.+ Accuracy of Sensor
-
Range
Accuracy
-
100.0mA
±3.5%rdg±2.2%f.s.+ Accuracy of Sensor
-
Other ranges
±3.0%rdg±2.0%f.s.+ Accuracy of Sensor
-
Range
Accuracy
-
100.0mA
±3.0%rdg±1.7%f.s.+ Accuracy of Sensor
-
Other ranges
±2.5%rdg±1.5%f.s.+ Accuracy of Sensor
-
Weight
Approx. 265g
-
Dimension
111(L)×60(W)×42(D)mm
-
Current range
8146 (30A type) : 100.0/1000mA/10.00/30.0A 8147 (70A type) : 100.0/1000mA/10.00/70.0A 8148 (100A type) : 100.0/1000mA/10.00/100.0A 8121 (100A type) : 10.00/100.0A 8122 (500A type) : 50.00/500.0A 8123 (1000A type) : 100.0/1000A 8128/8135 (5A type) : 5.000A/(50.00A) 8127 (100A type) : 10.00A/100.0A 8126 (200A type) : 20.00A/200.0A 8125 (500A type) : 50.00A/500.0A 8124 (1000A type) : 100.0A/1000A 8130 (1000A type) : 100.0/1000A
-
Voltage range
8309 (600V type) : 600.0V
-
Auto power off
Power-off function operates automatically after a switch remains for 3min. (when recording is stopped)
-
Recording mode
Normal, Trigger, Capture, Power Quality Analysis
-
Measuring method
True RMS
-
Operating system
Successive Approximation (CH1 single synchronized sampling)
-
Sampling interval
Normal/Trigger mode : approx. 1.65ms/CH Capture mode : approx. 0.55ms (waveform: at every 1.1ms) P.Q.A mode : approx. 0.55ms
-
Low battery warning
Battery mark display (in 4 levels)
-
Applicable standards
IEC 61010-1:2001 CAT III 300V Pollution degree2 IEC 61326 (EMC standard)
-
Included Accessories
7148 (USB cable), 9118 (Carrying case), Alkaline battery LR6×4pcs, PC software "KEW LOG Soft 2", Instruction manual, Quick manual, Install manual, USB Notice sheet
-
Optional Accessories
8146/8147/8148 (Leakage & Load current Clamp Sensor), 8121/8122/8123 (Load current Clamp Sensor), 8124/8125(*1)/8126(*2)/8127(*3)/8128 (Load current Clamp Sensor), 8130(*4)/8135 (Flexible Clamp Sensor), 8309 (Voltage sensor) 7185 (Extension cable for sensor), 8320 (AC Adapter), 9135 (Carrying bag),
-
Over-range indication
"OL" mark is displayed when exceeding the measuring range
-
RMS measuring interval
approx. 100ms
-
Number of input channel
3ch
-
Possible measurement time
Approx. 10 days (with alkaline LR6 batteries)
-
Rated max. working voltage
AC 9.9Vrms, 14V peak value